Control Options

Basic EC Enclosure

Basic - EC enclosures

  • IP66 plastic enclosure
  • Flip-up window for access to controller & fuses
  • Main lockable isolator
  • Carelir33 Universal controller
  • 0-10V output + 2 relays
  • Integrated PID closed loop logic
  • DIN railmounted transformer
  • DIN railmounted Power (green) & Fault (red) lamp
  • 2 motors per MCB (fuse)
  • NTC temperature sensor or pressure transducer
  • DIN rail terminals for ..
  • Fans
  • Power & faultindication
  • Remote On/Off of Controller

Optional

  • Modbus card – Supervision of controller only
Premium EC Enclosure

Premium - EC enclosures

  • IP66 plastic enclosure
  • Flip-up window for access to controller & fuses
  • Main lockable isolator
  • Carel pCO5+ Electronic PLC featuring …
  • 0-10V output
  • Digital ModBuscontrol of EC fans
  • BMS SupervisoryModBus port
  • Supports 4 stages FlexPad or FlexSpray
  • Integrated PID closed loop logic
  • Fullyprogrammable
  • DIN railmounted transformer
  • DIN railmounted Power (green) & Fault (red) lamp
  • 2 motors per MCB (fuse)
  • NTC ambient temperature sensor
  • NTC fluid temperature sensor or pressure transducer
  • DIN rail terminals for ..
  • Fans
  • Power & faultindication

Optional

  • LONworks card
  • BACnet card
  • KNX card
Basic Controller ir33

Basic Controller ir33

Controls EC fan speed via

  • PID closed loop logiccompares …
  • Fluid leaving temperature with …
  • Desired Set Point temperature generating …
  • Scaled 0-10 V signal

Additionally if FlexPad/Spray fitted …

  • Can trigger 1 or 2 relays to activate 1 or 2 stage wet system
  • The minimum operating period for eachwetstage is alsoprogrammable
Premium Controller pCO5

Premium Controller pCO5

Controls EC fan speed via …

  • PID closed loop logiccompares …
  • Fluid leaving temperature with …
  • Desired Set Point temperature generating …
  • Digital Modbus signal

Additionally if FlexPad/Spray fitted …

  • Can activate up to 4 relays to control a 4 stage wet system
  • Monitors the ambient temperature to provide frost protection and control the switch point temperatures
  • and much more …
FController

FController

  • Speed control, for trouble-free parallel operation of motors without shielded motor cables.
  • Pole effective sinusoidal filter. Operation without electromagnetic noise is possible.
  • No danger to the motors from voltage peaks, bearing currents, etc.

Attributes and special features:

  • Energy saving
  • No electronic motor noise
  • universal integrated control functionality.
Safety Switch

Safety Switch

  • Optional safety switch mounted on each fan to cut power to individual cooler sections if needed
Common Terminal

Common Terminal

  • Break-proof and shock resistant junction box